What is Open Circuit Test of Transformer ? Phasor Diagram & Calculation


     The performance ( efficiency, regulation, losses ) of a transformer is best judged if the following four parameters of its equivalent circuit are known :


(i) The equivalent resistance R01 as referred to the primary.

     The equivalent resistance R02 as referred to as secondary.


(ii) The equivalent leakage reactance X01 as referred to the primary.

     The equivalent leakage reactance X02 as referred to as secondary.


(iii) The core-loss resistance Ro ( parallel circuit ). and


(iv) The magnetising reactance Xo ( parallel circuit ).


     These four parameters or constants of a transformer equivalent circuit can be determined by the following two tests :

(a) Open-circuit test and

(b) Short-circuit test.


     These tests are very simple and cheap to perform because we can find the required information without actually loading the transformer. 



Open Circuit Test :


     The aim of the test is to determine the iron-loss or core-loss and no-load current Io which is helpful in finding Ro and Xo. The amount of power wasted in the core of a transformer can be obtained by this test.


      In this test one winding usually, high voltage winding is left open and the other ( L.V. side ) is connected to normal voltage supply as shown in the figure. Since normal voltage is applied to the primary, the normal flux will be set up in the core hence normal core-loss will occur which are measured by the wattmeter.


     As no current flows in the open secondary, the no-load primary current Io is small ( usually 3 to 10 of full-load current ), the primary copper loss is negligibly small and nil in secondary. Hence, the O.C. test gives core loss alone practically ( i.e., wattmeter reading ) and is the same for all loads.

Open Circuit Test of Transformer

     Sometimes, a high resistance voltmeter is connected across secondary to read secondary induced e.m.f. which helps to find the transformation ratio K.

Open Circuit Test of Transformer

     Transformer vector diagram is same as the no-load condition of a transformer as shown in the figure. If  Wo is the wattmeter reading,

Therefore,


     Since no-load current Io is very small therefore pressure coils of the wattmeter and voltmeter should be connected such that the current taken by them should not flow through the current coil of the watt-meter.



Separation of Hysteresis and Eddy Current Loss :


The core loss or iron loss consists of two parts

(i) Hysteresis loss 

Wh  =  P Bm1.6  f   watt / m3

(ii) Eddy current loss 

We  =  Q Bm2  f2   watt / m3

Where P, Q are two constants

     Bm  =  maximum flux density (T)

        f   =  frequency (Hz)


The total iron loss is given by

Wi  =  Wh + We 

    =  P Bm1.6  f  +  Q Bm2  f2

     

     Observation table to perform open-circuit on the transformer is shown below. Where no-load current can be calculated from the ammeter, total power loss ( i.e., iron loss in core ) is calculated through wattmeter, and the voltage applied is known by the voltmeter.


S.No.

Primary Rated Voltage V1
(volts)

No-load Current Io
(amp)

Wattmeter Readings (iron loss) Wo
(watt)

Secondary Induced Voltage V2
(volts)

Readings oberved from the test



Why Open Circuit Test is Performed on L.V. Side only ?


     The main thing is that an open circuit of a transformer is performed on any side of the transformer i.e., either on H.V. ( high voltage ) or L.V. ( low voltage ). But there are some benefits while performing O.C. test on L.V. side of the transformer.


     The aim of this test is to determine the no-load losses i.e., core loss at rated voltage. The term rated voltage means we have to apply the rated value of the voltage on L.V. side. This rated value of voltage is smaller ( 440V, 11kV  ) when compared to H.V. side ( 33kV, 132kV, and above ).


     So when we prefer H.V. side to test it becomes harder, costlier, and care must be taken while performing the test. Because the equipment ( measuring instruments ) used for tests i.e., to apply high voltages about 33kV, 132kV, and above becomes costlier. And precautions must be taken with proper insulation to the body to avoid shocks which may lead to death.


     The turns on the L.V. side of the transformer are less than the turns present on the H.V. side. Hence the power loss ( i.e., due to copper loss ) is less almost negligible on the L.V. side of the transformer when it is on no-load. 


     As we know that the open circuit test is to determine the core loss. Thus when a rated voltage is applied on the L.V. side power loss occurred is very small. Therefore, the wattmeter reads only the core loss component of the transformer. 
  



Post a Comment

0 Comments